Assessment of the Effect the Height and Relative Position of Support Insulation Components Have on the Insulation Electrical Strength

  • Aleksey R. KORYAVIN
  • Ol'ga V. VOLKOVA
Keywords: support insulation, cascade flashovers, electrical strength, positive polarity switching impulse

Abstract

The article presents the results from studies of the effect the height and relative position of extra high voltage class support insulation components have on the insulation electrical strength when subjected to positive polarity switching impulses, at which the insulation minimum permissible overall dimensions are determined. It is shown that the highest values of the insulation flashover voltage are achieved when a leader discharge develops along purely air trajectories: screen--pedestal or screen-- plane. A similar result is obtained in the case of cascade flashovers from the screen over the column elements if the upper insulator structural height is significantly larger than that of the lower one. The reverse mutual arrangement of these insulators leads to a significant drop in the insulation flashover voltage during cascade flashovers. It is shown that at the final jump onset moment, the main contribution to the insulation flashover voltage value is introduced by the voltage drop across positive streamers, which is directly proportional to the length of these streamers. Hence it follows that the ambiguous effect of the height and mutual arrangement of the support insulation components on the insulation electrical strength during cascade flashovers is mainly due a significant difference in the lengths of the positive streamer zones at the final jump onset. With the upper insulator height equal to 2.7 m, the length of positive streamers at this moment is commensurable with the length of streamers when the flashover develops along purely air trajectories, whereas decreasing the upper insulator height by almost a half entails a significant decrease in the streamer lengths. Measures to eliminate undesirable cascade flashovers and ensure the highest electrical strength of support insulation are proposed.

Author Biographies

Aleksey R. KORYAVIN

(All-Russian Electrotechnical Institute – Branch of FSUE ”RFNC-VNIITF named after academ. E.I. Zababakhin”, Moscow, Russia) – Chief Scientific Officer, Dr. Sci. (Eng.)

Ol'ga V. VOLKOVA

(All-Russian Electrotechnical Institute – Branch of FSUE ”RFNC-VNIITF named after academ. E.I. Zababakhin”, Moscow, Russia) – Leading Researcher, Cand. Sci. (Eng.)

References

1. ГОСТ Р 52034-2008. Изоляторы керамические опорные на напряжение свыше 1000 В. Общие технические условия. М.: Стандартинформ, 2009, 28 с.
2. Александров Г.Н., Иванов В.Л. Изоляция электрических аппаратов высокого напряжения. Л.: Энергоатомиздат, 1984, 208 с.
3. Слуцкин Л.С. Исследование электрической прочности опорной изоляции выключателей серии ВНВ. – Электричество, 1978, № 10, с. 74–77.
4. Белоедова И.П. и др. Расчет электрических полей устройств высокого напряжения. М.: Издательский дом МЭИ, 2008, 249 с.
5. Базелян Э.М., Горин Б.Н., Левитов В.И. Физические и инженерные основы молниезащиты. Л.: Гидрометеоиздат, 1978, 223 с.
6. Ларионов В.П. Основы молниезащиты. М.: Знак, 1999, 103 с.
7. Ларионов В.П. Молниезащита. Часть 1. – Электричество, 1999, № 4, с. 51–58.
8. Syssoev V.S., Shcherbakov Yu.V. Electrical Strength of Ultra-Long Air Gaps, 2001, DOI:10.4271/2001-01-2898.
9. Gallimberti I., et al. Fundamental Processes in Long Air Gap Discharges. – C. R. Physique, 2002, No. 3, pp. 1335–1359.
10. Carrara G., Thione L. Switching surge strength of large air gaps: A physical approach. – IEEE Transactions on Power Apparatus and Systems, 1976, No. 2, pp. 512–524, DOI:10.1109/T-PAS.1976.32131.
11. Carrara G., Pigini A., Thione L. Switching Impulse Insulation Strength of Multi-Electrode Air Gaps. Application of the «Leader Inception Approach» to the Determination of the Switching Impulse Strength of Multi-Electrode Air Insulation. – Colloquium CIGRE, 1975, 33–75(SC).
12. Горин Б.Н., Шкилев А.В. Развитие электрического разряда в длинных воздушных промежутках при импульсном напряжении положительной полярности. – Электричество, 1974, № 2, с. 29–38.
13. Волкова О.В., Корявин А.Р. К оценке минимальной электрической прочности длинных воздушных промежутков. – Электричество, 1980, № 3, с. 46–47.
14. Корявин А.Р. Минимальная электрическая прочность длинных воздушных промежутков с высоковольтным электродом различной формы. – Электротехника, 1983, № 4, c. 23–26.
#
1. GОSТ R 52034-2008. Izolyatory keramicheskie opornye na napryazhenie svyshe 1000 V. Obshchie tekhnicheskie usloviya (Ceramic Support Insulators for Voltage over 1000 V. General Specifications). М.: Standartinform, 2009, 28 p.
2. Aleksandrov G.N., Ivanov V.L. Izolyatsiya elektricheskih apparatov vysokogo napryazheniya (Insulation of High Voltage Electrical Devices). L.: Energoatomizdat, 1984, 208 p.
3. Slutskin L.S. Elektrichestvo – in Russ. (Electricity), 1978, No. 10, pp. 74–77.
4. Beloedova I.P., et al. Raschet elektricheskih poley ustroystv vysokogo napryazheniya (Calculation of Electric Fields of High Voltage Devices). М.: Izdatel'skiy dom MEI, 2008, 249 p.
5. Bazelyan E.M., Gorin B.N., Levitov V.I. Fizicheskie i inzhenernye osnovy molniezashchity (Physical and Engineering Fundamentals of Lightning Protection). L.: Gidrometeoizdat, 1978, 223 p.
6. Larionov V.P. Osnovy molniezashchity (Basics of Lightning Protection). М.: Znak, 1999, 103 p.
7. Larionov V.P. Elektrichestvo – in Russ. (Electricity), 1999, No. 4, pp. 51–58.
8. Syssoev V.S., Shcherbakov Yu.V. Electrical Strength of Ultra-Long Air Gaps, 2001, DOI:10.4271/2001-01-2898.
9. Gallimberti I., et al. Fundamental Processes in Long Air Gap Discharges. – C. R. Physique, 2002, No. 3, pp. 1335–1359.
10. Carrara G., Thione L. Switching surge strength of large air gaps: A physical approach. – IEEE Transactions on Power Apparatus and Systems, 1976, No. 2, pp. 512–524, DOI:10.1109/T-PAS.1976.32131.
11. Carrara G., Pigini A., Thione L. Switching Impulse Insulation Strength of Multi-Electrode Air Gaps. Application of the «Leader Inception Approach» to the Determination of the Switching Impulse Strength of Multi-Electrode Air Insulation. – Colloquium CIGRE, 1975, 33–75(SC).
12. Gorin B.N., Shkilev A.V. Elektrichestvo – in Russ. (Electricity), 1974, No. 2, pp. 29–38.
13. Volkova О.V., Koryavin А.R. Elektrichestvo – in Russ. (Electricity),1980, No. 3, pp. 46–47.
14. Koryavin А.R. Elektrotekhnika – in Russ. (Electrical Engineering), 1983, No. 4, pp. 23–26.
Published
2022-01-10
Section
Article